BS6396 is the British standard covering the installation of electrical systems in all furniture except special purpose workstations in laboratories or workshops.
BS6396 defines in detail the requirements for the safe use of electrical power sockets (up to 250V), supplied from either the fixed mains wiring via a 13A fused plug or from batteries at a nominal voltage not exceeding 48Vd.c. It also covers areas such as cable management and the segregation of power and data cables.
NOTE: Any power distribution systems that are connected to the building installation by anything other than a 13A BS1363 plug or a supply derived from batteries installed within the furniture should follow the requirements of BS7671.
BS6396 limits the number of BS1363 13A sockets connected to a single supply to either:
• No more than 6 sockets fused at 3.15A
• No more than 4 sockets fused at 5A
BS6396 also specifies the number of Extra Low Voltage (ELV)outlets allowed. In addition to the above permitted max number of AC sockets, up to 150W output of ELV is allowed.
If more than 150W is required then:
• For every 3.15A socket removed you can add up to 500W output of ELV power
• For every 5A socket removed you can add up to 700W output of ELV power.
Socket resettable fuses/thermal overloads should be either inaccessible without the use of a tool, trip free or inaccessible unless the load is disconnected.
Resettable fuse, covered by power plug, requires load to be disconnected before resetting. Highest safety level
Resettable fuse, covered by power plug, requires load to be disconnected before resetting. Highest safety level
Resettable fuses, accessible without a tool are only acceptable if they are TRIP FREE. Check with supplier
Tool release fuses can be used in place of thermal overloads. no positional requirement Acceptable safety level
For power sockets mounted directly in furniture with no external housing, the furniture requires earthing
For power mounted in plastic insulated housing, the furniture does not require earthing
For power encased in an earthed metal housing, the furniture does not require earthin
For power mounted in plastic insulated housing, the furniture does not require earthing
OE products are supplied with an external earth point as standard, but can be provided without if requested.
Furniture should allow for suitable cable management. Cable management systems should be free from sharp edges to protect cabling. Grommet holes should be adequately sized to allow cables to pass through easily. Cable bend radius should be kept to minimum to prevent damage to cables. Cable supports may be used in place of cable management, cable supports should have no more than a maximum of 300mm gap between supports.
Cable management to manage cables and house power module(s)
Cable segregation should be allowed for within cable management to separate power cables from other cables such as ELV, data and telecommunications cables.
Inverters for use with battery systems should be no more than 500W capacity. Battery voltage should be no more than 48V DC. Battery inverter systems must comply with BS EN IEC 62040-1 or BS EN IEC 62368-1.
When using power sockets with a battery system an RCD is required to protect the user. RCD’s should not be rated more 30mA
• Name, trademark of manufacturer or vendor BS6396
• If furniture is earthed or not and if so where. Where instructions are located. The rating of the system
• Max current rating
• Supply cable labelled with connection requirements
• A declaration that the system cannot be reconfigured or changed without referring to the manufacturer’s instruction beforehand
• If furniture contains batteries, the information must state battery type, for indoor or outdoor use and that manufacturer’s instructions are followed
OE House,
Calder Park,
Thomas Maddison Ln,
Durkar,
Wakefield
WF4 3GH
OE Showroom
1a Briset Street
London
EC1M 5NR
UK
Cookie | Duration | Description |
---|---|---|
cookielawinfo-checkbox-analytics | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Analytics". |
cookielawinfo-checkbox-functional | 11 months | The cookie is set by GDPR cookie consent to record the user consent for the cookies in the category "Functional". |
cookielawinfo-checkbox-necessary | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookies is used to store the user consent for the cookies in the category "Necessary". |
cookielawinfo-checkbox-others | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Other. |
cookielawinfo-checkbox-performance | 11 months | This cookie is set by GDPR Cookie Consent plugin. The cookie is used to store the user consent for the cookies in the category "Performance". |
viewed_cookie_policy | 11 months | The cookie is set by the GDPR Cookie Consent plugin and is used to store whether or not user has consented to the use of cookies. It does not store any personal data. |